    how deep to bury thermo pex for oWB?

    I've heard conflicting stories and would like some input from those of you that have an OWB. How deep did you bury it? I was thinking like only 2' mainly due to the mountainous rocky terrain here where I live. I have heard anywhere from 18" up to 4 friggin feet!! No way I get get that deep here without a big arse trencher!

  2. #2
    Arboristsite MVP
    Reputation Reputation Reputation Reputation Reputation Reputation
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    MS-310's Avatar
    Join Date
    Nov 2005
    Location
    MI
    Posts
    730
    Credits
    0
    Keep it deep about 42", if you keep the temp up on the outside of the pipe it will lose less heat....
    Thanks Jack,

    Are web site. www.grantswoodshop.com

  3. #3
    Senior Member
    Reputation Reputation Reputation Reputation
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation

    Join Date
    Aug 2008
    Location
    PA
    Posts
    460
    Credits
    37
    I'm also in PA...I'll be using thermopex from CB...my dealer said at least 12" and much more than that isn't needed...it's rated to run ON the ground and he's done that for winter installs then buries in the spring....snow doesn't melt off it above ground so I can see why going very deep isn't needed. I'd say it depends on your insulation of the pex your using....weak insulation go deeper, good stuff not as much need.

  4. #4
    Senior Member
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    fletcher0780's Avatar
    Join Date
    Apr 2008
    Location
    Northeast CT
    Posts
    444
    Credits
    10
    It really depends on your water table. If you ground is dry down to 42" put it there, go as deep as the water table will allow. I wouldn't bury any shallower than 18" even if you have a high water table.

  5. #5
    Senior Member
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation

    Join Date
    May 2008
    Location
    NE Pa. ( Poconos )
    Posts
    448
    Credits
    93
    What no one seems to be mentioning is that according to the National Weather Service in our area ( I live in the Poconos of NE Pa. ) the frost line is 21
    inches. Since your pipe is well insulated the depth doesnt much matter. Zoning regs probably require 2 ft for the electric line and you dont need it deeper than that. Finally and also important, make sure the outside pipe ( pvc or drain ) is seamless so that water doesnt get in.
    Good luck..


  6. #6
    Arboristsite MVP
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation

    Join Date
    Jan 2005
    Location
    Ohio
    Posts
    1,785
    Credits
    63
    Mine is Urecon but I think the insulating factor is close to same. I planned on 30" but we found a huge rock that we had to go over and the line is only about 24" there. Been in service over two winters now and at no time have I ever been able to see any difference in the snow cover over the line so I would assume heat loss is minimal. Id put it in as deep as you can without a huge hassle and forget it.
    Just an old farm boy whos been saw'en a while.

    Woodmaster 4440
    Stihl & Shindaiwa saws
    Shop built processor

    No more Stihls until no more flippy caps

  7. #7
    Arboristsite MVP
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    jeeptj19992001's Avatar
    Join Date
    Mar 2008
    Location
    cny
    Posts
    1,252
    Credits
    420
    i would go down below frost line, for construction, the frost line for that area if i recall correctly is 42". you can call your code officals for that info.
    Last edited by jeeptj19992001; 09-09-2008 at 09:31 AM.

  8. #8
    Senior Member
    Reputation Reputation

    Join Date
    Aug 2008
    Location
    Montoursville PA
    Posts
    102
    Credits
    0
    I'll probably use the CB thermopex

  9. #9
    Junior Member
    Reputation

    Join Date
    Aug 2008
    Location
    New Castle, PA
    Posts
    17
    Credits
    10

    How Deep

    Hi Madspeed,

    We installed an uninsulated 3/4 inch underground water line from the house to the barn, a total of 200 feet, buried 36 inches in 1998 here in WPA. It has never frozen and we have never had a problem, so when we installed the insulated pex piping for the OWB, we only went down to 24 inches to top of pipe/conduit. The electrical conduit was placed just above the water pipe, about a 2-4 inches. It is only 65 feet from the house. There is no temperature drop. We also placed masonry sand around the pipe before backfilling. Someone on here on another thread said that should also help keep the pipe warm. Did the same with the barn water line. I have also read about putting rigid insulation above the pipe; not sure if that would help. Also, the comment about ground water (and drainage water) is correct. Try to keep the pipe in dry soil. Good luck digging!
    Stihl Farm Boss 029
    Heatmor CSS 100
    Kabota L2500 w/ splitter

  10. #10
    Senior Member
    Reputation Reputation

    Join Date
    Aug 2008
    Location
    Montoursville PA
    Posts
    102
    Credits
    0
    I have one section where there will be running ground water over my pipe, do you think I should SLEEVE it with a larger diameter pipe and insulate between them?

  11. #11
    Arboristsite MVP
    Reputation Reputation
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    rx7145's Avatar
    Join Date
    Jun 2007
    Location
    Ashland Ohio
    Posts
    716
    Credits
    11
    I have Urecon and only went down a foot. No problems.
    Stihl MS 441 Magnum 25'' bar Full chisel skip
    Stihl MS 290 20" Bar (also have 16'' & 18'' bars) Full chisel
    Stihl MS 170
    Stihl MS 192T
    Stihl 009
    American CLS AM-30HH Logsplitter - 4hp electric/8hp Briggs
    Central Boiler 4436 Not only is it a heat source, its a lifestyle.
    Chevy K2500 6.5L TD
    Load-Trail 10.4k GVW 80"x12' Dump trailer.
    Quote Originally Posted by b1rdman View Post
    I rejected the Dems theories decades ago and now that the Republicans are inching ever so close to those ideals I reject them too.

  12. #12
    Arboristsite MVP
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    mtfallsmikey's Avatar
    Join Date
    Feb 2008
    Location
    Mt. Falls Va.
    Posts
    3,501
    Credits
    620
    I went down 36-38" on both loops. Another increasingly popular method is to foam the trench with the lines inside, but not any real cost savings...my CB dealer sells their insulated lines now for $12 / ft.
    "Not a sermon, just a thought"

    What's your heat loss?

    STIHLS
    2013 Stihl calendar
    Enough saws to do the job, lookin' for more..

    Pioneer RA-450D

    Macs, Homies, TMTL
    Central CB5036 OWB
    President Emeritus: Hang 'Em High Chainsaw Club of Mt. Falls

  13. #13
    Senior Member
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    fletcher0780's Avatar
    Join Date
    Apr 2008
    Location
    Northeast CT
    Posts
    444
    Credits
    10
    Quote Originally Posted by Madspeed View Post
    I have one section where there will be running ground water over my pipe, do you think I should SLEEVE it with a larger diameter pipe and insulate between them?
    I would, if water gets inside your outer jacket and makes contact with the pex it will wick away a lot of heat.

  14. #14
    Senior Member
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation Reputation
    LTREES's Avatar
    Join Date
    Sep 2007
    Location
    PA
    Posts
    474
    Credits
    6
    Ground water + pex-pipe = loss of heat
    definitely insulate between the pipes, insulation I assume is better the an air gap in between. But, then again, thermo-pex (CB) can stay on the ground in the snow. Maybe just run it straight through your wet land. Call a CB dealer.

  15. #15
    Senior Member
    Reputation
    Reputation Reputation Reputation Reputation Reputation Reputation

    Join Date
    Jul 2008
    Location
    Michigan Thumb
    Posts
    363
    Credits
    20
    i went down 48" just because that is the frost line here, the central boiler and heatmore guy told me 18" but, i just figured if i am digging with a backhoe i might as well keep going. Besides that i like to run a backhoe so the deeper i dug the longer i got to play
    Ms 360
    Ms 361
    Heatmor 200css[/B][/COLOR]
    Iron and Oak BH4003
    Moorbark Firewood conveyor

    Life is a puzzle sometimes you have to bend over, pick up the pieces and get back to work.

    "Dont wish for it, Work for it"
    -Cros-Lex sports team logo-



    Profile

Page 1 of 3 123 LastLast

Thread Information

Users Browsing this Thread

There are currently 1 users browsing this thread. (0 members and 1 guests)

Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •  
Page generated in 0.26561 seconds with 43 queries [Server Loads: 0.97 1.23 : 1.55]